6. Remote temperature sensor connections – (optional)
Important! The remote temperature sensor must be SCI type.
Table 6.1 - N.TC. Sensor: Temperature ~ Resistance Characteristics
Temp °C
7.2 10.0
12.8
15.6 18.3 21.1 23.9 26.7 29.4 32.2
Temp °F
45 50 55 60 65 70 75 80 85 90
Res. k 115.8 100.9 88.1 77.1 67.7 59.6 52.5 46.4 41.2 36.6
The default from factory is INTERNAL SENSOR.
6.1 Remote temperature sensor switch configuration
1. Move DIP switches 1,5 and 6 as in the picture. (See Table 5.1 for setting
Switches 2,3 and 4.)
Switch 1 - OFF
Switch 5 - ON
Switch 6 – OFF
2. Connect the temperature sensor leads to the T-T terminals.
3. Reconnect the front half of the thermostat to the base (applies 24Vac power).
4. Verify that the displayed temperature responds to the remote sensor.
The wire length for the remote sensor can be up to 100 feet (30 meters) with standard
thermostat cable (not less than 22 gauge).
If the distance is greater than 100 feet then the wire MUST be shielded type, 20-22 gauge,
twisted pair.
1 2 3 4 5 6