22
15. Offset Settings
The Offset is used for field calibration of the measured temperature if necessary.
• Press and hold (6 seconds) the On/Off button to turn the thermostat OFF.
• Using the “+” and “-“ buttons set the temperature set-point to 60°F, and wait
until the display stops flashing.
• Press and hold the Select button (10 sec.) until “OFFS” and the Offset number
(a number between –6…+6) will appear (not flashing) on the display.
• Change the Offset for ambient temperature using the “+” and “-“ buttons.
• Press the Select button again to return to normal display mode.
The default offset is “0”