9.2 Set the damper cycling CLOSE time (“dC”).
a. Press the Select button until “dC” appears on display.
b. Using the “+” and “-“ buttons adjust the damper cycling
CLOSE time.
The number is the minutes the ventilation damper will be
closed after the damper had been open and the fan is still
operating for any reason.
Range 1-480 minutes – Default 20 minutes.
10. Fan over-run after cooling status (“FC”)
The purpose of not allowing the fan to operate immediately after a cooling operation is to reduce
moisture re-evaporation from the cooling coil back into the living space. For climates where the
cooling coil generally remains dry, this option can be turned ON to cause the fan to operate for an
additional 60 seconds after a cooling operation to get more cooling effect.
a. Press the Select button until “FC” appears on display.
b. Using the “+” and “-“ buttons adjust the fan over-run after
cooling status – select ON or OFF.
ON causes the fan to continue to run for 60 sec after a
cooling operation has ended.
Default - OFF