8
A B
A
B
5.4 Jumpers explanation
Jumper 1: Complete Reset of the unit.
For complete reset:
• Move JMP1 to position B.
• Wait 15 seconds.
• Return JMP1 to position A.
JMP1 Default from factory:
Jumper 2: NOT IN USE.
JMP2 Default from factory:
Leave it closed!
Jumper 10: Enable or disable Auto change-over capability
• Enable Auto change-over – JMP10 in position A (default from factory).
• Disable Auto change-over – JMP10 in position B.
Default from factory: