16
9. Ventilation Damper Cycling
The purpose of cycling the ventilation damper is to limit the possibility of over-ventilating, which could
cause unnecessary space conditioning energy to be used. The damper will open when the fan comes
on, but if the fan stays on longer than needed for the introduction of ventilation air, the damper will
automatically close; it will then re-cycle for as long as the fan continues to operate. The damper
OPEN and CLOSED times are set in Steps 9.1 (“dO”) and 9.2 (“dC”). However, if “CALC” was
selected in Step 8, then Steps 9.1 (“dO”) and 9.2 (“dC”) will be skipped, and damper cycling times will
be automatically calculated according to the fan duty cycle and total period selected in Step 8.2 (“Fd”
and “Ft”).
9.1 Set the damper cycling OPEN time (“dO”).
a. Press the Select button until “dO” appears on display.
b. Using the “+” and “-“ buttons adjust the damper cycling
OPEN time.
The number is the maximum minutes the ventilation damper
will be open each time the fan is energized. 0 disables
damper cycling – meaning the damper will never open.
Range 0-480 minutes – Default 10 minutes.