16. Troubleshooting for Technician
Problem Solution
Check the thermostat for 24 VAC,
remove the front cover and test between Rc/Rh to C.
Check for good wiring connections at:
Rh (24 VAC for heat), Rc (24 VAC for cool), C (common).
The display is blank
If you are using one transformer for cool and heat, check that
the jumper is installed between Rc and Rh. Check that all
screws terminals are tight.
Check the Rc connection
Cool does not switch on
Check the Y1 connection
Check the Rh connection
Heat does not switch on
Check the W1 connection
In heat mode, unit blows cool air
Check the Auto Fan settings. The unit may be set to FAN
(shown in the display).
The unit displays low temperature
(32°F) all the time
The unit is not sensing the remote sensor.
The unit displays high temperature
(92°F) all the time
The unit is has a short circuit in the remote sensor.
The display shows the word
"PROGRAM" without the name of
the program period (wake, sleep,
etc)
The unit is in Override mode because the temperature set-point
was manually adjusted. The name of the program period will
reappear when the next program period starts.
The word “FAN” flashes without
Heat or Cool
This does not indicate a fault. It indicates that fan cycling is
active for ventilation and whole-house comfort mixing.
Displayed ambient temperature is
not accurate
Adjust the offset. See section 15. above.