Table 5.1 – DIP switch selection
DIP Switch settings
FUNCTION 1 2 3 4 5 6
Internal temp. sensor
1
ON x x x OFF ON
Remote temp. sensor OFF x x x ON OFF
Electric
1
x x OFF x x x
Oil/Gas x x ON x x x
3 min. compressor delay
1
x x x OFF x x
No compressor delay x x x ON
2
x x
Programmable
1
x OFF x x x x
Non-Programmable x ON x x x x
x = Disregard
1
= Factory Defaults
2
= FOR TEST ONLY
5.2 DIP Switch Operation
The DIP switch has 6 pins.
Each pin can be ON (top) or OFF (bottom). In the picture, pins 1 and 6 are ON, and pins 2 to 5 are OFF
5.3 Fan Explanation (DIP switch 3)
Fan control "electric”
Fan will activate immediately with heating and cooling.
Fan control "oil/gas”
Fan will activate immediately with cooling only. Fan will not be activated by the thermostat for heating.
Heating unit will activate the fan in AUTOFAN mode.